Visonic SMD-426 PG2 PowerG Wireless Two-way Photoelectric Smoke Detector (New Old Stock, Boxed)
- Model: Visonic SMD-426 PG2 (SMD-426/427 PG2 series), 100outlets old stock, boxed w/ manual, mount base & accessories.
- Use: Pro security alarm add-on; photoelectric smoke detection, 85dB local alarm + wireless transmit to panel; PowerG 2-way FHSS/AES-128 encryption, fits Visonic PowerMaster series alarm systems (NOT standalone, needs compatible panel).
- Features: Self-testing, tamper, low-battery, long battery life (old stock: advise battery check/replace), DO NOT PAINT, EN/UL certified.
- Cond: NOS, unused (box wear), complete; pro install req; needs compatible panel.
- Note: Fire security part; authentic OEM (no return except authenticity/mismatch); verify panel compatibility (PowerG/PowerMaster); battery aging normal for old stock, You may need a new Battery: 3V CR123A
- Made in Taiwan.
SMD-426 PG2 (photoelectric smoke detector) is an automatic fire detector with integral audible signal for open area protection, designed to sense smoke (not flame) and fitted with a PowerG type transceiver.
SMD-426 PG2 provides early warning of developing fire by sounding an alarm with its built-in alarm horn, and by transmitting a coded alarm signal to a PowerG receiver or to a compatible wireless alarm control panel.
It must be borne in mind, though that effective pre-warning of fire accidents is only possible if the detector is located, installed and maintained as described here.
In alarm condition, the buzzer sound can be stopped for 12 minutes by pressing the
TEST/MUTE switch. It will not restore the alarm condition, but will temporarily silence the
buzzer while you correct the condition. After 12 minutes, the detector restarts the alarm
buzzer sound.
Note: The TEST/MUTE switch functions as TEST switch (in normal operation) or as MUTE switch (in alarm condition).
The detector can also operate as a siren to indicate a fire alarm in other areas covered by
the alarm system, or to indicate burglar alarm events, as configured through the control panel (see the PowerMaster Installer Guide).
The tamper switch actuator (Figures 9a and 9b) is pressed against the bracket when the unit is attached to the bracket. Removal of the unit from the bracket causes the switch contacts to open, creating a tamper event, which is reported by the transceiver to the alarm system control panel.
Note: When the tamper switch is opened the detector becomes not ready for operation.